API RP 2350 Overfill Protection for Storage Tanks in Petroleum Facilities - Third Edition

Список продуктов
Данный раздел/документ содержится в продуктах:

 

American Petroleum Institute

Overfill Protection for Storage Tanks in Petroleum Facilities - Third Edition
 N RP 2350

 

Annotation

 

Applicability

The scope of this recommended practice (RP) is specifically limited to tanks associated with marketing, refining, pipeline and similar facilities containing Class I or Class II petroleum liquids. This RP does not apply to:

• Underground storage tanks

• Aboveground tanks of 1320 U.S. gallons (5000 liters) or less

• Tanks that are integral to a process

• Tanks containing Class III liquids

• Tanks containing non-combustible liquids

• Service stations

• Loading or delivery from wheeled vehicles (such as tank trucks or railroad tank cars)

Relationship of This Recommended Practice to NFPA 30

This document was prepared to include consistency with NFPA 30-2003 Edition, Chapter 4.6, which includes the following requirements:

Aboveground tanks at terminals receiving transfer of Class I liquids from mainline pipelines or marine vessels shall follow formal written procedures to prevent overfilling of tanks utilizing one of the following methods of protection:

1. Tanks gauged at frequent intervals by personnel continuously on the premises during product receipt with frequent acknowledged communication maintained with the supplier so that flow can be promptly shut down or diverted.

2. Tanks equipped with a high-level detection device that is independent of any tank gauging equipment. Alarms shall be located where personnel who are on duty throughout product transfer can promptly arrange for flow stoppage or diversion.