IEC 60669-1 (REDLINE + STANDARD) Switches for household and similar fixed electrical installations – Part 1: General requirements - Edition 4.0
Данный раздел/документ содержится в продуктах:
- Техэксперт: Машиностроительный комплекс
- Картотека зарубежных и международных стандартов
- IEC 61084-1 Cable Trunking and Ducting Systems for Electrical Installations Part 1: General Requirements - Edition 1.0
- 29
- IEC 61084-1 Cable Trunking and Ducting Systems for Electrical Installations Part 1: General Requirements - Edition 1.0
- 29.060
- CEI EN 61439-6 Low-voltage switchgear and controlgear assemblies Part 6: Busbar trunking systems (busways)
- IEC 60570 Electrical supply track systems for luminaires - Edition 4.0
- CENELEC EN 61439-6 Low-voltage switchgear and controlgear assemblies - Part 6: Busbar trunking systems (busways)
- IEC 61084-2-4 Cable Trunking and Ducting Systems for Electrical Installations - Part 2: Particular Requirements - Section 4: Service Poles - Edition 1.0
- Картотека зарубежных и международных стандартов
International Electrotechnical Commission
Switches for household and similar fixed electrical installations – Part 1: General requirements - Edition 4.0
N 60669-1 (REDLINE + STANDARD)
Annotation
This part of IEC 60669 applies to manually operated general purpose functional switches, for alternating current (AC) only with a rated voltage not exceeding 440 V with a rated current not exceeding 63 A, intended for household and similar fixed electrical installations, either indoors or outdoors.
For switches provided with screwless terminals, the rated current is limited to 16 A.
NOTE 1 The rated current is limited to 16 A for switches provided with insulation piercing terminals (IPT’s) according to Annex D.
Switches covered by this document are, where applicable, intended for the control in normal use of all of the following loads:
– a circuit for a tungsten filament lamp load; – a circuit for an externally ballasted lamp load (for example LED, CFL, fluorescent lamp load);
– a circuit for a self ballasted lamp load (for example LEDi or CFLi); – a circuit for a substantially resistive load with a power factor not less than 0,95;
– a single phase circuit for motor load with a rated current not exceeding 3 A at 250 V (750 VA) and 4,5 A at 120 V (540 VA) and a power factor not less than 0,6. This applies to both switches rated not less than 10 A that have not undergone additional tests and to momentary switches rated not less than 6 A that have not undergone additional tests.
NOTE 2 In the following country the suitability of a switch intended to control the inrush current of a motor shall be tested: AU.
This document also applies to boxes for switches, with the exception of mounting boxes for flush-type switches.