ASHRAE 170 ADD M Ventilation of Health Care Facilities
Данный раздел/документ содержится в продуктах:
- Техэксперт: Машиностроительный комплекс
- Картотека зарубежных и международных стандартов
- NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations - Effective Date: 8/21/2013
- ASHRAE 52.2 ERTA Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size
- AWWA C151/A21.51 Ductile-Iron Pipe, Centrifugally Cast
- AWWA C111/A21.11 Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings
- IAPMO CMC California Mechanical Code - First Printing: July 1, 2013
- UL 181B UL Standard for Safety Closure Systems for Use with Flexible Air Ducts and Air Connectors - Third Edition
- UL 399 UL Standard for Safety Drinking Water Coolers - Seventh Edition; Reprint with revisions through and including October 18, 2013
- UL 498 BULLETIN UL Standard for Safety Attachment Plugs and Receptacles - COMMENTS DUE: November 30, 2015
- UL 1026 UL Standard for Safety Household Electric Cooking and Food Serving Appliances - Sixth Edition; Reprint with revisions through and including August 1, 2016
- IAPMO UMC UNIFORM MECHANICAL CODE - Twenty-Seventh Edition; First Printing 01/2015
- Картотека зарубежных и международных стандартов
American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
Ventilation of Health Care Facilities
N 170 ADD M
Annotation
General Requirements
a. Locate humidifiers within air-handling units or ductwork to avoid moisture accumulation in downstream components, including filters and insulation.
b. A humidity sensor shall be provided, located at a suitable distance downstream from the steam injection source.
c. Controls shall be provided to limit duct humidity to a maximum value of 90% rh when the humidifier is operating.
d. Duct takeoffs shall not be located within the humidifier’s absorption distance.
e. Humidifier steam control valves shall be designed so that they remain off whenever the air-handling unit is not in operation.