ASTM E1966 Standard Test Method for Fire-Resistive Joint Systems

Список продуктов
Данный раздел/документ содержится в продуктах:

 

ASTM International

Standard Test Method for Fire-Resistive Joint Systems
 N E1966

 

Annotation

 

This fire-test-response test method measures the performance of joint systems designed to be used with fire rated floors and walls during a fire endurance test exposure. The fire endurance test end point is the period of time elapsing before the first performance criteria is reached when the joint system is subjected to one of two time-temperature fire exposures.

The fire exposure conditions used are either those specified by Test Method E119 for testing assemblies to standard time-temperature exposures or Test Method E1529 for testing assemblies to rapid-temperature rise fires.

This test method specifies the heating conditions, methods of test, and criteria for the evaluation of the ability of a joint system to maintain the fire resistance where hourly rated fire-separating elements meet.

Test results establish the performance of joint systems during the fire-exposure period and shall not be construed as having determined the joint systems suitability for use after that exposure.

This test method does not provide quantitative information about the joint system relative to the rate of leakage of smoke or gases or both. However, it requires that such phenomena be noted and reported when describing the general behavior of joint systems during the fire endurance test but is not part of the conditions of compliance.

Potentially important factors and fire characteristics not addressed by this test method include, but are not limited to:

The performance of the fire-resistive joint system constructed with components other than those tested.