ASTM D1868 Standard Test Method for Detection and Measurement of Partial Discharge (Corona) Pulses in Evaluation of Insulation Systems
Данный раздел/документ содержится в продуктах:
- Техэксперт: Машиностроительный комплекс
- Картотека зарубежных и международных стандартов
- DIN VG 85289 Hose fitting with flange - DN 150, PN up to 16; Text in German and English
- 23
- DIN VG 85289 Hose fitting with flange - DN 150, PN up to 16; Text in German and English
- 23.040
- DIN VG 85289 Hose fitting with flange - DN 150, PN up to 16; Text in German and English
- 23.040.70
- DIN VG 85289 Hose fitting with flange - DN 150, PN up to 16; Text in German and English
- 47
- DIN VG 85289 Hose fitting with flange - DN 150, PN up to 16; Text in German and English
- 47.020
- DIN VG 85289 Hose fitting with flange - DN 150, PN up to 16; Text in German and English
- DIN VG 95955-4 Hoses for fuelling and pipelines - Part 4: Generic specification; Text in German and English
- IEC 60167 Methods of Test for the Determination of the Insulation Resistance of Solid Insulating Materials - Edition 1.0
- BSI BS EN 62631-1 Dielectric and resistive properties of solid insulating materials Part 1: General - CORR: October 31, 2016
- CENELEC EN 60505 Evaluation and qualification of electrical insulation systems
- Картотека зарубежных и международных стандартов
ASTM International
Standard Test Method for Detection and Measurement of Partial Discharge (Corona) Pulses in Evaluation of Insulation Systems
N D1868
Annotation
This test method covers the detection and measurement of partial discharge (corona) pulses at the terminals of an insulation system under an applied test voltage, including the determination of partial discharge (corona) inception and extinction voltages as the test voltage is raised and lowered. The test method is also useful in determining quantities such as apparent charge and pulse repetition rate together with such integrated quantities as average current, quadratic rate and power. The test method is useful for test voltages ranging in frequency from zero (direct voltage) to approximately 2000 Hz.
The test method is directly applicable to a simple insulation system that can be represented as a two-terminal capacitor (1), (2) .
The test method is also applicable to (distributed parameter) insulation systems such as high-voltage cable. Consideration must be given to attenuation and reflection phenomena in this type of system. Further information on distributed parameter systems of cables, transformers, and rotating machines will be found in Refs. (1), (2), (3), (4), (5), (6), (7), (8), and (9).2 (See AEIC CS5-87, IEEE C57 113-1991, IEEE C57 124-1991, and IEEE 1434-2005.)
The test method can be applied to multi-terminal insulation systems, but at some loss in accuracy, especially where the insulation of inductive windings is involved.
This standard does not purport to address all of the safety problems, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. Specific precaution statements are given in Sections 8 and 14.