IEC 62821-3 Electric cables – Halogen-free, low smoke, thermoplastic insulated and sheathed cables of rated voltages up to and including 450/750 V – Part 3: Flexible cables (cords) - Edition 1.0
Данный раздел/документ содержится в продуктах:
- Техэксперт: Машиностроительный комплекс
- Картотека зарубежных и международных стандартов
- BSI BS 7629-1 Electric cables - Specification for 300/500 V fire resistant screened cables having low emission of smoke and corrosive gases when affected by fire - Part 1: Multicore and multipair cables
- BSI BS EN 50267-2-2 Common Test Methods for Cables Under Fire Conditions - Tests on Gases Evolved During Combustion of Materials From Cables - Part 2-2: Procedures - Determination of Degree of Acidity of Gases for Materials by Measuring pH and Conductivity
- BSI BS EN 50264-1 Railway applications - Railway rolling stock power and control cables having special fire performance - Part 1: General requirements
- BSI BS EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flame
- BSI BS EN 50525-3-11 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke
- IEC 60719 Calculation of the Lower and Upper Limits for the Average Outer Dimensions of Cables with Circular Copper Conductors and of Rated Voltages up to and Including 450/750 V - Edition 2.0
- BSI BS EN 50525-3-11 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke
- BSI BS EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flame
- BSI BS EN 50264-1 Railway applications - Railway rolling stock power and control cables having special fire performance - Part 1: General requirements
- BSI BS EN 50267-2-2 Common Test Methods for Cables Under Fire Conditions - Tests on Gases Evolved During Combustion of Materials From Cables - Part 2-2: Procedures - Determination of Degree of Acidity of Gases for Materials by Measuring pH and Conductivity
- 13
- BSI BS 7629-1 Electric cables - Specification for 300/500 V fire resistant screened cables having low emission of smoke and corrosive gases when affected by fire - Part 1: Multicore and multipair cables
- BSI BS EN 50267-2-2 Common Test Methods for Cables Under Fire Conditions - Tests on Gases Evolved During Combustion of Materials From Cables - Part 2-2: Procedures - Determination of Degree of Acidity of Gases for Materials by Measuring pH and Conductivity
- BSI BS EN 50264-1 Railway applications - Railway rolling stock power and control cables having special fire performance - Part 1: General requirements
- BSI BS EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flame
- BSI BS EN 50525-3-11 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke
- IEC 60719 Calculation of the Lower and Upper Limits for the Average Outer Dimensions of Cables with Circular Copper Conductors and of Rated Voltages up to and Including 450/750 V - Edition 2.0
- BSI BS EN 50525-3-11 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke
- BSI BS EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flame
- BSI BS EN 50264-1 Railway applications - Railway rolling stock power and control cables having special fire performance - Part 1: General requirements
- BSI BS EN 50267-2-2 Common Test Methods for Cables Under Fire Conditions - Tests on Gases Evolved During Combustion of Materials From Cables - Part 2-2: Procedures - Determination of Degree of Acidity of Gases for Materials by Measuring pH and Conductivity
- 13.220
- BSI BS 7629-1 Electric cables - Specification for 300/500 V fire resistant screened cables having low emission of smoke and corrosive gases when affected by fire - Part 1: Multicore and multipair cables
- BSI BS EN 50267-2-2 Common Test Methods for Cables Under Fire Conditions - Tests on Gases Evolved During Combustion of Materials From Cables - Part 2-2: Procedures - Determination of Degree of Acidity of Gases for Materials by Measuring pH and Conductivity
- BSI BS EN 50264-1 Railway applications - Railway rolling stock power and control cables having special fire performance - Part 1: General requirements
- BSI BS EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flame
- BSI BS EN 50525-3-11 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke
- IEC 60719 Calculation of the Lower and Upper Limits for the Average Outer Dimensions of Cables with Circular Copper Conductors and of Rated Voltages up to and Including 450/750 V - Edition 2.0
- BSI BS EN 50525-3-11 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke
- BSI BS EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flame
- BSI BS EN 50264-1 Railway applications - Railway rolling stock power and control cables having special fire performance - Part 1: General requirements
- BSI BS EN 50267-2-2 Common Test Methods for Cables Under Fire Conditions - Tests on Gases Evolved During Combustion of Materials From Cables - Part 2-2: Procedures - Determination of Degree of Acidity of Gases for Materials by Measuring pH and Conductivity
- 13.220.99
- BSI BS 7629-1 Electric cables - Specification for 300/500 V fire resistant screened cables having low emission of smoke and corrosive gases when affected by fire - Part 1: Multicore and multipair cables
- BSI BS EN 50267-2-2 Common Test Methods for Cables Under Fire Conditions - Tests on Gases Evolved During Combustion of Materials From Cables - Part 2-2: Procedures - Determination of Degree of Acidity of Gases for Materials by Measuring pH and Conductivity
- BSI BS EN 50264-1 Railway applications - Railway rolling stock power and control cables having special fire performance - Part 1: General requirements
- BSI BS EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flame
- BSI BS EN 50525-3-11 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke
- IEC 60719 Calculation of the Lower and Upper Limits for the Average Outer Dimensions of Cables with Circular Copper Conductors and of Rated Voltages up to and Including 450/750 V - Edition 2.0
- BSI BS EN 50525-3-11 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke
- BSI BS EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flame
- BSI BS EN 50264-1 Railway applications - Railway rolling stock power and control cables having special fire performance - Part 1: General requirements
- BSI BS EN 50267-2-2 Common Test Methods for Cables Under Fire Conditions - Tests on Gases Evolved During Combustion of Materials From Cables - Part 2-2: Procedures - Determination of Degree of Acidity of Gases for Materials by Measuring pH and Conductivity
- BSI BS 7629-1 Electric cables - Specification for 300/500 V fire resistant screened cables having low emission of smoke and corrosive gases when affected by fire - Part 1: Multicore and multipair cables
- BSI BS 7629-1 Electric cables - Specification for 300/500 V fire resistant screened cables having low emission of smoke and corrosive gases when affected by fire - Part 1: Multicore and multipair cables
- BSI BS 7629-1 Electric cables - Specification for 300/500 V fire resistant screened cables having low emission of smoke and corrosive gases when affected by fire - Part 1: Multicore and multipair cables
- 29
- BSI BS 7629-1 Electric cables - Specification for 300/500 V fire resistant screened cables having low emission of smoke and corrosive gases when affected by fire - Part 1: Multicore and multipair cables
- BSI BS EN 50267-2-2 Common Test Methods for Cables Under Fire Conditions - Tests on Gases Evolved During Combustion of Materials From Cables - Part 2-2: Procedures - Determination of Degree of Acidity of Gases for Materials by Measuring pH and Conductivity
- BSI BS EN 50264-1 Railway applications - Railway rolling stock power and control cables having special fire performance - Part 1: General requirements
- BSI BS EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flame
- BSI BS EN 50525-3-11 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke
- IEC 60719 Calculation of the Lower and Upper Limits for the Average Outer Dimensions of Cables with Circular Copper Conductors and of Rated Voltages up to and Including 450/750 V - Edition 2.0
- BSI BS EN 50525-3-11 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke
- BSI BS EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flame
- BSI BS EN 50264-1 Railway applications - Railway rolling stock power and control cables having special fire performance - Part 1: General requirements
- BSI BS EN 50267-2-2 Common Test Methods for Cables Under Fire Conditions - Tests on Gases Evolved During Combustion of Materials From Cables - Part 2-2: Procedures - Determination of Degree of Acidity of Gases for Materials by Measuring pH and Conductivity
- BSI BS 7629-1 Electric cables - Specification for 300/500 V fire resistant screened cables having low emission of smoke and corrosive gases when affected by fire - Part 1: Multicore and multipair cables
- BSI BS EN 50267-2-2 Common Test Methods for Cables Under Fire Conditions - Tests on Gases Evolved During Combustion of Materials From Cables - Part 2-2: Procedures - Determination of Degree of Acidity of Gases for Materials by Measuring pH and Conductivity
- BSI BS EN 50264-1 Railway applications - Railway rolling stock power and control cables having special fire performance - Part 1: General requirements
- BSI BS EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flame
- BSI BS EN 50525-3-11 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke
- IEC 60719 Calculation of the Lower and Upper Limits for the Average Outer Dimensions of Cables with Circular Copper Conductors and of Rated Voltages up to and Including 450/750 V - Edition 2.0
- BSI BS EN 50525-3-11 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke
- BSI BS EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flame
- BSI BS EN 50264-1 Railway applications - Railway rolling stock power and control cables having special fire performance - Part 1: General requirements
- BSI BS EN 50264-1 Railway applications - Railway rolling stock power and control cables having special fire performance - Part 1: General requirements
- BSI BS EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flame
- BSI BS EN 50525-3-11 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke
- IEC 60719 Calculation of the Lower and Upper Limits for the Average Outer Dimensions of Cables with Circular Copper Conductors and of Rated Voltages up to and Including 450/750 V - Edition 2.0
- BSI BS EN 50525-3-11 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke
- BSI BS EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flame
- BSI BS EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flame
- BSI BS EN 50525-3-11 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke
- IEC 60719 Calculation of the Lower and Upper Limits for the Average Outer Dimensions of Cables with Circular Copper Conductors and of Rated Voltages up to and Including 450/750 V - Edition 2.0
- BSI BS EN 50525-3-11 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke
- BSI BS EN 50525-3-11 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke
- IEC 60719 Calculation of the Lower and Upper Limits for the Average Outer Dimensions of Cables with Circular Copper Conductors and of Rated Voltages up to and Including 450/750 V - Edition 2.0
- IEC 60719 Calculation of the Lower and Upper Limits for the Average Outer Dimensions of Cables with Circular Copper Conductors and of Rated Voltages up to and Including 450/750 V - Edition 2.0
- IEC 62821-3 Electric cables – Halogen-free, low smoke, thermoplastic insulated and sheathed cables of rated voltages up to and including 450/750 V – Part 3: Flexible cables (cords) - Edition 1.0
- IEC 62821-2 Electric cables – Halogen-free, low smoke, thermoplastic insulated and sheathed cables of rated voltages up to and including 450/750 V – Part 2: Test methods - Edition 1.0
- BSI BS 7629-1 Electric cables - Specification for 300/500 V fire resistant screened cables having low emission of smoke and corrosive gases when affected by fire - Part 1: Multicore and multipair cables
- Картотека зарубежных и международных стандартов
International Electrotechnical Commission
Electric cables – Halogen-free, low smoke, thermoplastic insulated and sheathed cables of rated voltages up to and including 450/750 V – Part 3: Flexible cables (cords) - Edition 1.0
N 62821-3
Annotation
This part of IEC 62821 applies to flexible cables for connection to appliances, insulated and sheathed with halogen-free thermoplastic compound and having low emission of smoke and corrosive gases when exposed to fire.
NOTE For some types of flexible cables, the term "cord" is used.
Low emission of smoke is checked in accordance with IEC 61034-2.Low emission of corrosive gases is checked as part of the check for absence of halogens (see Annex B of IEC 62821-1:2015).
The cables are of rated voltages U0/U up to and including 300/500 V.
Circular cables and flat cables are included.
The maximum conductor operating temperature for each of the cables in this standard is 70 °C.
IEC 62440 should be used as guidance on the safe use of cables in this standard.
Автоматический перевод:
Электрические кабели – низкий дым без Галогена, термопласт изолированные и вложенные в ножны кабели номинальных напряжений до и включая 450/750 V – Часть 3: Гибкие кабели (провода) - Издание 1.0