ULC CAN/ULC-S603-14 STANDARD FOR STEEL UNDERGROUND TANKS FOR FLAMMABLE AND COMBUSTIBLE LIQUIDS - Fourth Edition
Данный раздел/документ содержится в продуктах:
- Техэксперт: Машиностроительный комплекс
- Картотека зарубежных и международных стандартов
- ULC CAN/ULC-S653-06 STANDARD FOR ABOVEGROUND STEEL CONTAINED TANK ASSEMBLIES FOR FLAMMABLE AND COMBUSTIBLE LIQUIDS - Second Edition
- 23
- ULC CAN/ULC-S653-06 STANDARD FOR ABOVEGROUND STEEL CONTAINED TANK ASSEMBLIES FOR FLAMMABLE AND COMBUSTIBLE LIQUIDS - Second Edition
- 23.020
- 75
- ULC CAN/ULC-S676-15 STANDARD FOR REFURBISHING OF STORAGE TANKS FOR FLAMMABLE AND COMBUSTIBLE LIQUIDS - First Edition
- ULC CAN/ULC-S603-14 STANDARD FOR STEEL UNDERGROUND TANKS FOR FLAMMABLE AND COMBUSTIBLE LIQUIDS - Fourth Edition
- ULC CAN/ULC-S656-14 STANDARD FOR OIL-WATER SEPARATORS - Second Edition
- Картотека зарубежных и международных стандартов
Underwriters' Laboratories of Canada
STANDARD FOR STEEL UNDERGROUND TANKS FOR FLAMMABLE AND COMBUSTIBLE LIQUIDS - Fourth Edition
N CAN/ULC-S603-14
Annotation
Except as described in Clause 1.7, these minimum requirements cover single and double wall cylindrical steel, non-pressure tanks of the horizontal type that are used for the underground storage of flammable liquids and combustible liquids, that are compatible with the material of construction.
These minimum requirements cover double wall tanks with provision for leak detection monitoring of the interstice between the walls.
NOTE: The designs identified in this Standard are satisfactory for vacuum and/or electronic monitoring devices. (Refer to Figure 1.)
This Standard also provides design criteria for integral connections (connection rings/collars) for spill containment sumps or manway risers.
These minimum requirements cover tanks, which are fabricated, inspected and tested for leakage before shipment from the factory as completely assembled vessels.
NOTE: For the requirements for tanks provided with corrosion protection systems at the factory, refer to the Standard CAN/ULC-S603.1, Standard for External Corrosion Protection Systems for Steel Underground Tanks for Flammable and Combustible Liquids.
These minimum requirements cover tanks up to a maximum capacity of 250 000 L.
The requirements in this Standard are for the construction of stationary tanks and do not cover their installation, maintenance and operation. The installation, maintenance and operation of these tanks may be covered by any of, but not limited to, the following documents: