ASTM D877/D877M Standard Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using Disk Electrodes
Данный раздел/документ содержится в продуктах:
- Техэксперт: Машиностроительный комплекс
- Картотека зарубежных и международных стандартов
- ASTM G125 Standard Test Method for Measuring Liquid and Solid Material Fire Limits in Gaseous Oxidants
- 13
- ASTM G125 Standard Test Method for Measuring Liquid and Solid Material Fire Limits in Gaseous Oxidants
- 13.220
- ASTM G125 Standard Test Method for Measuring Liquid and Solid Material Fire Limits in Gaseous Oxidants
- 13.220.40
- 19
- ASTM D4895 Standard Specification for Polytetrafluoroethylene (PTFE) Resin Produced From Dispersion
- ASTM D2902 Standard Specification for Fluoropolymer Resin Heat-Shrinkable Tubing for Electrical Insulation
- ASTM D3636 REV A Standard Practice for Sampling and Judging Quality of Solid Electrical Insulating Materials
- ASTM D3394 Standard Test Methods for Sampling and Testing Electrical Insulating Board
- Картотека зарубежных и международных стандартов
ASTM International
Standard Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using Disk Electrodes
N D877/D877M
Annotation
This test method describes two procedures, A and B, for determining the electrical breakdown voltage of insulating liquid specimens. The breakdown test uses ac voltage in the power-frequency range from 45 to 65 Hz.
This test method is used to judge if the disk electrode breakdown voltage requirements are met for insulating liquids, as delivered from the manufacturer, that have never been filtered or dried. See Specification D3487, Specification D4652, Specification D6871 and Guide D5222 for the minimum specified electrical breakdown. This test method should be used as recommended by professional organization standards such as IEEE C57.106.
Limitations of the Procedures:
The sensitivity of this test method to the general population of contaminants present in a liquid sample decreases as applied test voltages used in this test method become greater than approximately 25 kV rms.
If the concentration of water in the sample at room temperature is less than 60 % of saturation, the sensitivity of this test method to the presence of water is decreased. For further information refer to RR:D27-1006.2
The suitability for this test method has not been determined for a liquid's viscosity higher than 900 cSt at 40°C.
Procedure Applications
Procedure A:
Procedure A is used to determine the breakdown voltage of liquids in which any insoluble breakdown products easily settle during the interval between the required repeated breakdown tests. These liquids include petroleum oils, hydrocarbons, natural and synthetic esters, and askarels (PCB) used as insulating and cooling liquids in transformers, cables, and similar apparatus.