ASTM D4245 Standard Specification for Ozone-Resistant Thermoplastic Elastomer Insulation For Wire and Cable, 90 °C Dry/75 °C Wet Operation
Данный раздел/документ содержится в продуктах:
- Техэксперт: Машиностроительный комплекс
- Картотека зарубежных и международных стандартов
- UL 444 UL Standard for Safety Communications Cables - Fourth Edition; Reprint with Revisions Through and Including April 30, 2015
- IEC 62680-2-3 Universal serial bus interfaces for data and power - Part 2-3: Universal Serial Bus Cables and Connectors Class Document Revision 2.0 - Edition 1.0
- 29
- IEC 62680-2-3 Universal serial bus interfaces for data and power - Part 2-3: Universal Serial Bus Cables and Connectors Class Document Revision 2.0 - Edition 1.0
- 29.220
- 33
- IEC 62680-2-3 Universal serial bus interfaces for data and power - Part 2-3: Universal Serial Bus Cables and Connectors Class Document Revision 2.0 - Edition 1.0
- 33.120
- 35
- ASTM D4565 Standard Test Methods for Physical and Environmental Performance Properties of Insulations and Jackets for Telecommunications Wire and Cable
- ASTM D2633 REV A Standard Test Methods for Thermoplastic Insulations and Jackets for Wire and Cable
- Картотека зарубежных и международных стандартов
ASTM International
Standard Specification for Ozone-Resistant Thermoplastic Elastomer Insulation For Wire and Cable, 90 °C Dry/75 °C Wet Operation
N D4245
Annotation
This specification covers an ozone-resistant insulating compound for electrical wire and cables 14 AWG and larger. This compound consists substantially of a thermoplastic elastomer.
This type of insulation is suitable for continuous operation at conductor temperatures not exceeding 90°C in dry locations and 75°C in wet locations. Operating voltages are not to exceed 2000 V. The minimum installation temperature is 40°C.
The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
In many instances the insulation material cannot be tested unless it has been formed around a conductor or cable. Therefore, tests are done on insulated wire or cable in this document solely to determine the relevant property of the insulation material and not to test the conductor or completed cable.
*A Summary of Changes section appears at the end of this standard
Автоматический перевод:
Стандартная спецификация для стойкой к озону изоляции термопластичного эластомера для провода и кабеля, 90 °C сушат/75 °C влажную операцию