ASTM E2750 Standard Guide for Extension of Data from Penetration Firestop System Tests Conducted in Accordance with ASTM E814
Данный раздел/документ содержится в продуктах:
- Техэксперт: Машиностроительный комплекс
ASTM International
Standard Guide for Extension of Data from Penetration Firestop System Tests Conducted in Accordance with E814
N E2750
Annotation
This guide covers the extension of results obtained from fire tests performed in accordance with Test Method E814 to applications that have not been tested. Test Method E814 evaluates the duration for which test specimens will contain a fire, retain their integrity, or both during a predetermined fire test exposure. Firestops are intended for use in fire-resistive walls and floors that are evaluated in conformance with Test Method E119.
NOTE 1—Data obtained from firestops tested in accordance with Test Methods E119 with positive pressure can also be used.
This guide is based on principles involving the extension of test data using simple considerations. The acceptance of these principles and their application is based substantially on an analogous worst-case proposition.
These principles are only applicable to temperature conditions represented by the standard time-temperature curve described in Test Method E814, for systems falling within the scope of Test Method E814. This test method is a fire-testresponse standard.
The types of building constructions which are part of this guide are as follows: floors, walls, partitions, floor/ceiling and roof/ceiling assemblies.
This guide applies to:
a single penetrating item, or
multiple penetrating items.
This guide does not apply to joints systems tested to E119, E1966 and E2307.
Penetrating items can be one of the following: metallic pipe, non-metallic pipe, metallic tubing, non-metallic tubing, metallic conduit, non-metallic conduit, flexible metal conduit, cables, cable trays, bus ducts, insulated pipes, insulated tubing, insulated conduit, insulated and non-insulated ducts, and structural members.